CVE-2023-2186
criticalOn Triangle MicroWorks' SCADA Data Gateway version <= v5.01.03, an unauthenticated attacker can send a specially crafted broadcast message including format str…
Vendor / product: Trianglemicroworks — scada data gateway
On Triangle MicroWorks' SCADA Data Gateway version <= v5.01.03, an unauthenticated attacker can send a specially crafted broadcast message including format string characters to the SCADA Data Gateway to perform unrestricted memory reads.An unauthenticated user can use this format string vulnerability to repeatedly crash the GTWWebMonitor.exe process to DoS the Web Monitor. Furthermore, an authenticated user can leverage this vulnerability to leak memory from the GTWWebMonitor.exe process. This could be leveraged in an exploit chain to gain code execution.
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H Affected products
Weakness classification (CWE)
Source: NVD / CISA. “NVD-CWE-Other” and “NVD-CWE-noinfo” mean NVD could not assign a specific weakness.
Mitigation & advisories
No vendor advisory or patch reference tagged by NVD. Check the references below.
References
- https://www.trellix.com/en-us/about/newsroom/stories/research/industrial-and-manufacturing... trellixpsirt@trellix.com
- https://www.trellix.com/en-us/about/newsroom/stories/research/industrial-and-manufacturing... af854a3a-2127-422b-91ae-364da2661108